6.5 Inverter Protection Control
Inverter current protection control and radiation fin temperature control are performed to prevent
tripping due to an abnormality, or transient inverter overcurrent, and fin temperature increase.
In the case of multi-outdoor-unit system, each compressor performs these controls in the
following sequence.
Inverter overcurrent protection control
This control is performed for each inverter compressor.
Radiation fin temperature control
This control is performed for each inverter compressor.
Condition
RXQ6AR
RXQ8-12AR
RXQ14/16AR
M1C
M1C
M1C
M2C
A
more than 17.0 A
more than 27.5 A
more than 17.0 A
more than 27.5 A
B
less than 17.0 A
less than 27.5 A
less than 17.0 A
less than 27.5 A
C
more than 17.6 A
more than 27.5 A
more than 17.6 A
more than 27.5 A
Condition
All compressors
A
more than 110 °C
B
less than 107 °C
C
more than 114 °C
Normal control
Inverter current standby
Reduce compressor capacity
A
B
When occurring 3 times within 60
minutes, the error code
L8
is
output.
C
Normal control
Fin temperature standby
Reduce compressor capacity
When occurring 4 times within 60
minutes, the error code
L4
is output.
A
B
C
Summary of Contents for VRV X RXQ6-48ANR Series
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...