SiME341909EA
Troubleshooting by Error Code
Part 6 Service Diagnosis
193
5.23 Current Leakage Detection
Applicable
Models
All outdoor unit models
Error Code
E2
Sub code: -01 to -03
Method of Error
Detection
Current leakage is detected in the earth leakage detection circuit. Error is detected on the
outdoor unit main PCB.
Error Decision
Conditions
When leakage current is detected.
Supposed
Causes
Earth fault
Defective wiring with the current sensor
Temporary liquid back or refrigerant stagnation
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Correct the wiring.
Normal
(Keep operating)
It is possibly caused by
temporary oil return or
refrigerant stagnation.
(Perform maintenance
during long-term
shutdown such as a
power outage.)
Check
if the
connection to the
current sensor (T1A) is
correctly wired.
NO
Replace the compressor.
RXQ6-12AR: M1C
RXQ14/16AR: M1C, M2C
Defective compressor
insulation
YES
YES
Replace the corresponding
parts.
Defective
insulation of parts
other than the
compressor
YES
NO
NO
Turn OFF the power supply,
and then disconnect the
compressor lead wire.
Reconnect the wires, and
then reconnect the unit to the
power supply.
Summary of Contents for VRV X RXQ6-48ANR Series
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...