12
FXMQ-MFVJU EDUS39-900B-F10
8. Capacity Tables
FXMQ48MFVJU
Cooling
Outdoor air temperature
°FWB
°FDB
62
66
70
74
78
82
86
90
Capacity
MBh
MBh
MBh
MBh
MBh
MBh
MBh
MBh
67
13000
15900
71
13000
15900
18300
75
13000
15900
18300
23300
79
15900
18300
22900
83
18300
22900
37700
87
17900
22600
37300
48300
91
17900
22200
37000
48000
56200
95
21900
36600
47600
55800
59600
Heating
Outdoor air temperature
°FWB
°FDB
19
23
27
31
35
39
43
51
55
Capacity
MBh
MBh
MBh
MBh
MBh
MBh
MBh
MBh
MBh
22
32600
32600
-
-
-
-
-
-
-
32
-
-
30000
-
-
-
-
-
-
37
-
-
26600
26600
26600
-
-
-
-
42
-
-
-
-
21500
21500
21500
-
-
52
-
-
-
-
-
16800
16800
16800
-
57
-
-
-
-
-
-
12100
12100
12100
Note:
1. The above capacities are based on the following conditions:
Air discharge temperature setting: 64°F for cooling operation,
77°F for heating (factory setting).
Equivalent piping length: 25 ft.
Level difference: 0 ft.
2. The above capacities values are general average values which can be generated by each compressor operation level.
3. A value enclosed in
means rated capacity.
Summary of Contents for VRV Series
Page 1: ...Outdoor Air Processing Unit FXMQ MFVJU EDUS39 900B F10 202103 Engineering Data 60 Hz...
Page 2: ......
Page 7: ...5 FXMQ MFVJU EDUS39 900B F10 3 Dimensions FXMQ48MFVJU 3D065452A Unit in...
Page 8: ...6 FXMQ MFVJU EDUS39 900B F10 FXMQ72 96MFVJU 3D065453A Unit in...
Page 20: ...18 FXMQ MFVJU EDUS39 900B F10 10 Fan Performances FXMQ48MFVJU 3D065649B...
Page 21: ...19 FXMQ MFVJU EDUS39 900B F10 FXMQ72MFVJU 3D065650B...
Page 22: ...20 FXMQ MFVJU EDUS39 900B F10 FXMQ96MFVJU 3D065651B...
Page 26: ......
Page 27: ......