7. Electric Characteristics
FXMQ48-96MFVJU
Model
Power supply
IFM
Input (W)
SCCR
Hz
Volts
Voltage range
MCA
MOP
KW
FLA
Cooling Heating
FXMQ48MFVJU
60
208/230 V
Max. 253 V
Min. 187 V
2.1
15
0.380
1.7
359
359
SCCR kA rms,
Symmetrical
@600 V MAX: 5
FXMQ72MFVJU
3.6
15
0.380
2.9
548
548
FXMQ96MFVJU
4.1
15
0.380
3.3
638
638
Symbol:
MCA: Min. Circuit Amps (A)
MOP: Max. Overcurrent Protective Device (A)
KW: Fan Motor Rated Output (kW)
FLA: Full Load Amps (A)
IFM: Indoor Fan Motor
SCCR: Short-Circuit Current Rating
Note:
1. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MCA/MOP
MCA = 1.25 × FLA
MOP ≤ 4 × FLA
(Next lower standard fuse raring. Min. 15 A)
4. Select wire size based on the MCA.
C: 4D065596