
Check
SiAF332111E
356
Part 6 Service Diagnosis
6.16 Fan Motor Connector Check (Power Supply Cable)
CHECK 16
Check the fan motor connector according to the following procedure.
Outdoor unit
RXMQ6-12AR
1. Turn OFF the power supply.
2. Measure the resistance between phases of U, V, W at the motor side connectors (3-core
wire) to check that the values are balanced and there is no short circuiting, while connector
or relay connector is disconnected.
Indoor unit
FXMQ50-140PB
Measurement of power wire connector.
Remove the X1A connector from the fan PCB (A2P) and measure the resistance between the
U and V, V and W, and W and U phases of the motor connector (with five conductors) and
check that each phase are balanced (within a permissible dispersion range of ±20%)
Red
White
Black
W
V
U
Red (5)
— (4)
White (3)
— (2)
Black (1)
U
V
W
Connector power wire use (X1A)
Summary of Contents for VRV S RXQ4/5ARV1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...