Troubleshooting by Error Code
SiAF332111E
320
Part 6 Service Diagnosis
5.65 Address Duplication of Centralized Controller
Applicable
Models
All indoor unit models
Centralized controller
Error Code
UC
Method of Error
Detection
An indoor unit detects the same address as that of its own on any other indoor unit.
Error Decision
Conditions
The error decision is made as soon as the abnormality aforementioned is detected.
Supposed
Causes
Address duplication of centralized controller
Defective indoor unit PCB
Troubleshooting
Make setting change so that
the centralized address
w
ill
not
b
e d
u
plicated.
The centralized address is
d
u
plicated.
Caution
Be s
u
re to t
u
rn off the po
w
er s
w
itch
b
efore connecting or disconnecting
connectors, or parts may
b
e damaged.