SiAF332111E
Troubleshooting by Error Code
Part 6 Service Diagnosis
299
5.58 Power Supply Insufficient or Instantaneous Abnormality
5.58.1 Power Supply Insufficient or Instantaneous Abnormality (4/5 HP
Models)
Applicable
Models
RXQ4/5AR
Error Code
U2
Method of Error
Detection
The main circuit capacitor voltage of the inverter and the power supply voltage is checked.
Error Decision
Conditions
The main circuit capacitor of the tested inverter has abnormal voltage or the power supply
voltage is abnormal.
Supposed
Causes
Insufficient power supply
Instantaneous power failure
Defective outdoor fan motor
Defective outdoor unit main PCB
Summary of Contents for VRV S RXQ4/5ARV1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...