Field Settings for Outdoor Unit (6/8 HP Models)
Part 5 Field Settings and Test Operation
143
3.7 Eco Mode Setting
By connecting an external contact input in the input of mode configuration and external control
adaptor (sold separately), you may control Eco mode setting, limiting compressor operation
load and power consumption.
When Eco mode is set as unavailable (Outdoor unit external control adaptor is
unnecessary)
Eco mode control is unavailable during cooling operation.
When the Eco level of Eco mode control is set as Standard/Low or Eco mode control is
set as unavailable by external control adaptor
1. Connect the external control adaptor and short-circuit the input terminal TeS1 if necessary.
2. Set mode 2-11 (External Eco Setting) to
Eco setting by low noise level input or Eco
setting by demand input
according to the short-circuited terminal.
About Eco Level Setting
The upper limit of Te (target evaporation temperature) is changed based on the Eco level.
In case of VRTsmart control
The lowest temperature between the above and mode 2-76 VRTsmart control Te upper limit is
set.
In case of VRT control
The priority of each setting is as follows:
1. Mode 2-23 (Eco Control Unavailable Setting)
2. Mode 2-11 (External Eco Setting) and external control adaptor input
3. Eco mode setting
Setting description
Setting mode
Item
Condition
Description
External control adaptor Outdoor unit PCB
Eco level Standard
Eco level set as
Standard
by low noise
level
Short-circuit the low
noise level terminal in
the terminal TeS1
Set mode 2-11 to
Eco setting by low noise
level input
Eco level set as
Standard
by demand
control
Short-circuit the demand
input terminal 3 – C in
the terminal TeS1
Set mode 2-11 to
Eco setting by demand
input
Low
Eco level set as
Low
by demand control
Short-circuit the demand
input terminal 2 – C in
the terminal TeS1
Eco control unavailable
Eco control set as
unavailable by low
noise level
Open the low noise
level terminal in the
terminal TeS1
Set mode 2-11 to
Eco setting by low noise
level input
Eco control set as
unavailable by
demand control
Open the demand
input terminal in the
terminal TeS1
Set mode 2-11 to
Eco setting by demand
input
VRTsmart control
Mode 2-76: Te upper limit
Eco level
Standard
22°C
Low
9°C
VRT control
Mode 2-78: Te upper limit
Standard
High
Eco level
Standard
17°C
21°C
Low
16°C
20°C
Summary of Contents for VRV S RXQ4/5ARV1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...