SiAF332111E
Control for 6/8 HP Outdoor Unit
Part 4 Functions and Control
75
2.6 Protection Control
2.6.1 High Pressure Protection Control
This high pressure protection control is used to prevent the activation of protection devices due
to abnormal increase of high pressure and to protect compressors against the transient
increase of high pressure.
Cooling
The following control is performed in the entire system.
2.6.2 Low Pressure Protection Control
This low pressure protection control is used to protect compressors against the transient
decrease of low pressure.
Cooling
Because of common low pressure, the following control is performed in the system.
Normal control
Pc > 3.55 MPa
High pressure standby
Reduce compressor capacity step
Pc > 3.72 MPa
Pc < 3.04 MPa
When occurring 3 times within 40
minutes, high pressure switch is
activated without high pressure standby,
thus outputting the error code
E3
.
Pc: High pressure sensor detection
value for each outdoor unit.
Normal control
Pe < 0.35 MPa
Low pressure standby
Reduce compressor capacity step
Pe < 0.07 MPa
Pe > 0.40 MPa
When occurring 3 times within 60
minutes, the error code
E4
is output.
Pe: Low pressure sensor detection
value for master unit.
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...