SiAF332111E
Control for 6/8 HP Outdoor Unit
Part 4 Functions and Control
69
2.2 Stop Control
2.2.1 Abnormal Shutdown
In order to protect compressors, if any of the abnormal state occurs, the system will make "stop
with thermostat OFF" and the error will be determined according to the number of retry times.
(Refer to
Error Codes and Descriptions
on page 190 for the items to determine the error.)
2.3 Standby Control
2.3.1 Restart Standby
Used to forcedly stop the compressor for a period of 5 minutes, in order to prevent the frequent
ON/OFF of the compressor and equalize the pressure within the refrigerant system.
In addition, the outdoor fan carry out the residual operation for a while to accelerate pressure
equalizing and to suppress melting of the refrigerant to the evaporator.
2.3.2 Crankcase Heater Control
In order to prevent the refrigerant from melting in the compressor oil in the stopped mode, this
mode is used to control the crankcase heater.
Ta_30, Ta_60: Outdoor air temperature 30 minutes before and 60 minutes before,
respectively.
V1
V2
2Y350
0.05664
–0.15151
2Y420
0.03021
–0.08081
• Ta
26°C
• Ta > 26°C
• Time-up
• V2 < (Ta – Ta_30)/30 < V1
• V2 < (Ta – Ta_60)/60 < V1
Crankcase heater
OFF
Crankcase heater
ON
OR
&
• Ta > 26°C
• (Ta – Ta_30)/30
V1
• (Ta – Ta_60)/60
V1
&
• Ta > 26°C
• Time-up
• V2 < (Ta – Ta_30)/30 < V1
• V2 < (Ta – Ta_60)/60 < V1
OR
&
• Ta > 26°C
• (Ta – Ta_30)/30
V2
• (Ta – Ta_60)/60
V2
&
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...