Part 6 Service Diagnosis
357
6.17 Fan Motor Connector Check (Signal Cable)
CHECK 17
Check the fan motor connector according to the following procedure.
Outdoor Unit
RXQ4/5AR
1. Turn OFF the power supply.
2. Remove the connector (X106A) on the PCB to measure the resistance value.
Judgment criteria: resistance value between each phase is within ±20%
Indoor Unit
Resistance measuring points and judgment criteria.
FXMQ40PB, FXAQ-P
FXMQ50-140PB
Measurement of signal wire connector.
Remove the X2A connector and measure the resistance between GND and Vcc, Hw, Hv, or Hu
terminals of the motor connector (with five conductors).
White (1)
Orange (2)
Brown (3)
Blue (4)
— (5)
— (6)
Red (7)
FG
Vsp
Vcc
GND
—
—
Vdc
X106A
White (1)
Orange (2)
Brown (3)
Blue (4)
— (5)
— (6)
Red (7)
FG
Vsp
Vcc
GND
—
—
Vdc
Measuring points
Judgment criteria
1-4
1
or more
2-4
1
or more
3-4
1
or more
7-4
1
or more
Gray (5)
Pink (4)
Orange (3)
Blue (2)
Yellow (1)
GND
Vcc
Hw
H
V
H
U
Connector signal wire use (X2A)
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...