Troubleshooting by Error Code
SiAF332111E
298
Part 6 Service Diagnosis
5.57 Reverse Phase, Open Phase
Applicable
Models
RXMQ10/12AR
Error Code
U1
Method of Error
Detection
Each phase is detected by reverse phase detection circuit and it is determined whether the
phase is reversed or not.
Error Decision
Conditions
The power supply is in reverse phase, or T phase is in open phase.
Supposed
Causes
Power supply reverse phase
Power supply T phase open phase
Defective outdoor unit PCB
Troubleshooting
Is there an open
phase at the power supply
terminal (X1M) T phase of the
outdoor unit?
Operation is
normal if one phase of
power supply line phase is
replaced.
Fix the open phase.
Requires inspection of
field power supply.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
YES
NO
NO
Replace the outdoor unit
main PCB (A1P).
Power supply reverse phase.
After the phase replacement,
the countermeasures are
completed.
YES