Troubleshooting by Error Code
SiAF332111E
208
Part 6 Service Diagnosis
5.8 Power Supply Voltage Abnormality
5.8.1 Power Supply Voltage Abnormality (FXMQ-PB)
Applicable
Models
FXMQ-PB
Error Code
A8
Method of Error
Detection
Error is detected by checking the input voltage of the fan motor.
Error Decision
Conditions
When the input voltage of fan motor is 150 V or less, or 386 V or more.
Supposed
Causes
Defective power supply voltage.
Defective connection on signal line.
Defective wiring.
Instantaneous power failure, others.
Troubleshooting
YES
There are
problems on the
condition of power supply
described above.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Correct any fault.
NO
NO
YES
Check and correct each wiring.
It is possible there was an
external cause, such as
brownout or instantaneous
power failure.
Check the condition of the power
supply.
(1) Check if power supply voltage is
220-240 V ± 10%.
(2) Check if there is power open
phase or defective wiring.
(3) Check if power supply voltage
unbalance is within 6 V.
A8
Reoccurrence of
error.
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...