
Field Settings for Outdoor Unit (6/8 HP Models)
SiAF332111E
126
Part 5 Field Settings and Test Operation
3.3 Settings by BS Buttons
The following settings can be made using the BS buttons on the PCB.
Normal mode:
Blank: If no abnormality is detected and initialization of communication was completed.
Flashing combination of letter and number (4 digits): Error code detected by outdoor
control or trouble by communication.
Setting mode: Used to make changes to operating status, performance settings or address
setting.
Monitor mode: Used to verify contents of settings, quantity of units, current value of some
parameters during operation of outdoor unit.
Mode changing procedure can be selected using the MODE (BS1) button as shown
below:
MODE
BS1
SET
(TEST)
BS2
RETURN
(RESET)
BS3
Used to make
setting mode
changes.
Used to make
field settings.
7 segment display (SEG1-3)
BS buttons
Normal mode
Setting mode
Monitor mode
SEG1 SEG2 SEG3
Monitor mode
Press the
MODE
(BS1)
button once
Setting mode
Press and hold the
MODE (BS1)
button
for 5 seconds or more
Press the
MODE
(BS1)
button once
SEG1 SEG2 SEG3
SEG1 SEG2 SEG3
SEG1 SEG2 SEG3
Normal mode
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...