SiAF332111E
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
107
1.4.28 Individual Ventilation Setting
This is set to perform individual operation of heat reclaim ventilation using the remote
controller/central unit when heat reclaim ventilation is built in.
(Switch only when heat reclaim ventilation is built in.)
: Factory setting
1.4.29 Display of Error Codes on the Remote Controller
BRC1E Series
Error code (four digits) is displayed for limited products.
Select two-digit display if four-digit display is not preferred.
: Factory setting
1.4.30 Setting Restricted/Permitted of Airflow Block
The airflow block function cannot be enabled when closure material kit, fresh air intake kit,
separately installed natural evaporation type humidifier, or branch air duct is equipped, due to
the possibility of dew condensation.
This setting restricts the airflow block function, preventing that the airflow block is inadvertently
set to ON.
Ensure that “Airflow block restricted” is set when using the options listed above.
: Factory setting
1.4.31 Room Temperature Display
BRC1E Series
A "Detailed display screen" can be selected as the display screen. This setting is used if you do
not want to display "Room temperature display" on the "Detailed display screen".
: Factory setting
Mode
No.
First
Code No.
Second
Code No.
Contents
15 (25)
5
01
Normal
02
Individual
Mode
No.
First Code
No.
Second Code
No.
Contents
1b
4
01
—
02
Two-digit display
03
—
04
Four-digit display
Mode
No.
First
Code No.
Second
Code No.
Contents
1b
14
01
Airflow block permitted
02
—
03
—
04
—
05
Airflow block restricted
Mode
No.
First
Code No.
Second
Code No.
Contents
1c
0
01
Not displayed
02
Displayed
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...