
SiAF332111E
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
99
1.4.5 Time for Absence Area Detection
By selecting the energy-saving operation mode in the absence, the target temperature is shifted
to the energy-saving end by 1°C (maximum 2°C) after the state of absence continues for a
certain period of time.
Absent time defined for detection can be selected as follows:
: Factory setting
The set temperature displayed on the remote controller remains the same even if the target
temperature is shifted.
As soon as people are detected while the temperature is shifted, this control will be
cancelled (reset).
1.4.6 Dry Operation Time during VRTsmart Control
If you switch the operation mode to "Dry" while VRTsmart is enabled, the mode will
automatically switch to "Cooling" after a certain period of time is elapsed.
If you want to increase the duration of dry operation, change the Second code No. as
indicated in the following table.
Note 1) Increasing duration of dry operation degrades the energy efficiency
: Factory setting
Note 2) When group control is enabled, all indoor units in the same group have a same set value for
duration of dry operation.
1.4.7 Low Airflow Setting when Thermostat OFF during VRTsmart Control
This setting changes the airflow volume to LL in coordination with the VRTsmart control when
cooling thermostat OFF is set. Also, the airflow direction is changed to horizontal.
When disabled:
12 (22)-6 (the airflow volume setting when cooling thermostat OFF is enabled)
13 (23)-7 (the swing setting when cooling thermostat OFF is enabled) is as set
When enabled: LL when Te ≥ 7°C
: Factory setting
Mode
No.
First
Code No.
Second
Code No.
Contents
10 (20)
7
01
30 minutes
02
60 minutes
30 (60)
∗
60 (120)
∗
31
28
27
26
30
29
Elapsed time of absence (minutes)
Set temperature (°C)
Human detection
Cooling (at 28°C)
State of absence
∗
The values in parentheses represent the time
when Second code No. is
02
.
Mode
No.
First
Code No.
Second
Code No.
Contents
10 (20)
10
01
30 minutes
02
60 minutes
03
90 minutes
04
Continuous (not returning to cooling)
Mode
No.
First Code
No.
Second
Code No.
Contents
10 (20)
11
01
Disabled
02
Enabled
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...