SiAF332111E
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
97
1.4 Details of Field Settings for Indoor Unit
1.4.1 Filter Cleaning Sign Interval, Filter Type
When the setting 10 (20)-3 is set to
01
(Displayed), filter cleaning sign is displayed on the
remote controller after a certain period of operation time. This setting is used to change the
display interval of filter cleaning sign when the filter contamination is heavy.
The filter cleaning sign interval is determined as follows depending on the combination of Mode
No. 10 (20)-0 and 10 (20)-1.
Filter cleaning sign interval
: Factory setting
1.4.2 Remote Controller Thermistor
Select a thermistor to control the room temperature.
When the unit is not equipped with an infrared floor sensor:
: Factory setting
The factory setting for the Second code No. is
01
and room temperature is controlled by the
suction air thermistor for indoor unit and remote controller thermistor. When the Second code
No. is set to
02
, room temperature is controlled by the suction air thermistor. When the Second
code No. is set to
03
, room temperature is controlled by the remote controller thermistor.
Setting
10 (20)-1
01: Long life filter
02: Ultra long life filter
Filter contamination
heavy/light 10 (20)-0
Light
01
Heavy
02
Light
01
Heavy
02
Model
FXFSQ-AR
2,500 hrs.
1,250 hrs.
10,000 hrs.
5,000 hrs.
FXMQ-PB
FXMQ-AR
FXAQ-P
200 hrs.
100 hrs.
200 hrs.
100 hrs.
Mode
No.
First
Code No.
Second
Code No.
Contents
10 (20)
2
01
Remote controller thermistor and suction air thermistor
in indoor unit
02
Suction air thermistor in indoor unit
03
Remote controller thermistor
20
22
24
26
2
8
30
32
34
36
21
19
17
23
25
27
29
31
33
35
37
In cooling
S
u
ction air temperat
u
re (˚C)
S
u
ction air
thermistor
S
u
ction air
thermistor
S
u
ction air
thermistor
S
u
ction air
thermistor
Remote controller
thermistor
Remote controller
thermistor
Set temper
at
u
re (˚C)
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...