SiUS342004EB
Startup Control
Part 4 Functions and Control
86
4.2 Startup Control in Heating
DSH : Discharge pipe superheating degree
Pc : High pressure sensor detection value
Pe : Low pressure sensor detection value
0 Hz
+10 rps/10 sec.
A
B
C
D
E
0 pulse
Step 4
Step 8
OR
&
PI control
Compressor
(M1C)
Electronic expansion
valve (main)
(Y1E)
Fan motor
(M1F + M2F)
Frequency step up
5 sec. interval
Initial
opening
Pc – Pe > 0.42 MPa (60.9 psi)
DSH > 12°C (21.6°F)
Pc – Pe > 0.32 MPa (46.4 psi)
20 rps or more
Pc – Pe > 0.17 MPa (24.7 psi)
&
19
24
29
38
57
Frequency
(rps)
16.4
16.4
18
24
36
A
B
C
D
E
RXYQ72-120XA
RXYQ72-120XB
RXYQ144/168XA
RXYQ144/168XB