SiUS342004EB
Main/Sub Setting
Part 3 Remote Controller
66
3.2 BRC1H71W
3.2.1 Main and Sub Controller
INFORMATION
and check the wiring.
INFORMATION
After re-designating a controller, the system requires a power reset.
INFORMATION
The following functions are not available for sub controllers:
• “Auto” operation mode
•
• Filter auto clean
• Setback temperature setpoints
• Draft prevention
If a sub controller does not display the home screen 2 minutes after its designation, turn off the power
Individual airflow direction
a
b
c
d
a
Outdoor unit
b
Indoor unit
c
Main remote controller
d
Sub remote controller
• On the information screen, main/sub status is indicated by the following icons:
Icon
Description
Main
Sub
INFORMATION
It is only possible to use a main and a sub controller of the same type.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...