SiUS342004EB
Check
Part 6 Service Diagnosis
376
4.13 Electronic Expansion Valve Coil Check
CHECK 18
Measure the connector pin-to-pin resistance and make sure that the resistance value is within the
range listed in the table below.
Determine the type according to the connector wire color and measure the resistance.
Outdoor Unit
Y1E, Y3E, Y4E
Y7E
Measuring points
Judgment criteria
Y1E, Y3E
Y4E
1 - 6
120-180
35-55
2 - 6
3 - 6
4 - 6
Measuring points
Judgment criteria
1 - 5
120-180
2 - 5
3 - 5
4 - 5
White (1)
Yellow (2)
Orange (3)
Blue (4)
— (5)
Red (6)
White (1)
Yellow (2)
Orange (3)
Blue (4)
Red (5)