SiUS342004EB
Troubleshooting by Error Code
Part 6 Service Diagnosis
356
3.75 Climate Talk Communication System Combination Error
(After Initial Setting for Communication Completes)
Applicable
Models
CXTQ-TA
Error Code
UH-06
Method of Error
Detection
Detects the type of the devices constituted in Climate Talk Communication.
Error Decision
Conditions
The error decision is made when any of the following conditions is established once the initial
setting for communication with the gas furnace completes and after elapsing 4 minutes after the
power is turned ON.
Two or more gas furnaces are detected.
Any unit other than the gas furnace is detected.
Supposed
Causes
Connection of wrong devices
Two or more gas furnaces are connected to one CXTQ-TA.
Troubleshooting
YES
Caution
Be sure to turn off the po
w
er s
w
itch before connecting or disconnecting
connectors, or parts may be damaged.
N
O
Replace the CXTQ-TA PCB
or the gas furnace PCB.
Connect the gas furnace of
proper combination. Do not
connect any other devices.
Any
device other
than the gas
furnace of proper
combination is connected
to 1 and 2
terminals of
X
8
A.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...