SiUS342004EB
Troubleshooting by Error Code
Part 6 Service Diagnosis
352
3.72 System Not Set Yet
Applicable
Models
All indoor unit models
All outdoor unit models
Error Code
UF
Method of Error
Detection
On check operation, the number of indoor units in terms of transmission is not corresponding to that
of indoor units that have made changes in temperature.
Error Decision
Conditions
The error is determined as soon as the abnormality aforementioned is detected through checking
the system for any erroneous connection of units on the check operation.
Supposed
Causes
Improper connection of transmission wiring between indoor-outdoor units and outdoor-outdoor
units
Failure to execute check operation
Defective indoor unit PCB
Stop valve is not opened
Troubleshooting
Is
indoor-outdoor
and outdoor-outdoor
unit transmission
wiring normal?
Is
indoor-outdoor and
outdoor-outdoor unit
transmission wiring
normal?
Replace the indoor unit PCB.
Wiring check operation may
not have been carried out
successfully.
After fixing incorrect wiring,
press and hold the
RETURN
(BS3)
button on the outdoor
unit main PCB for 5 seconds.
∗
The unit will not run for up to
12 minutes.
YES
NO
YES
NO
NO
YES
Is the check
operation
carried out?
Open the stop valve.
YES
NO
Are the stop
valves opened?
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...