SiUS342004EB
Troubleshooting by Error Code
Part 6 Service Diagnosis
302
3.45 Thermistor Abnormality
Applicable
Models
All outdoor unit models
Error Code
H9, J3, J5, J6, J7, J8, J9
Method of Error
Detection
Detect according to temperature detected with individual thermistors.
Error Decision
Conditions
The system is in operation and the thermistor causes wiring disconnection or short circuit in it.
Supposed
Causes
Defective connection of thermistor
Defective thermistor
Defective outdoor unit main PCB
Troubleshooting
Thermistor is
connected to the
connector.
Replace the outdoor unit main
PCB (A1P).
Connect the connector and turn
ON again.
NO
NO
Replace the thermistor (
1).
YES
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Resistance
is normal when
measured after
disconnecting the
thermistor from the
outdoor unit
main PCB.
CHECK 11
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...