Troubleshooting by Error Code
SiUS342004EB
301
Part 6 Service Diagnosis
Note(s)
3.44 Outdoor Fan PCB Abnormality
Applicable
Models
All outdoor unit models
Error Code
H7
Method of Error
Detection
Detect with current sensor value.
Error Decision
Conditions
When the current sensor shows abnormality.
Supposed
Causes
Defective fan PCB (A5P, A6P)
Troubleshooting
1. Fan PCB and connectors
Properly connect the connector.
NO
YES
Replace the relevant fan motor.
(M1F, M2F)
NO
YES
Check for fan PCB applicable to the error code
H7
while in
monitor mode.
H7-21/23/25: Fan PCB for M1F Master / Slave 1 / Slave 2
H7-22/24/26: Fan PCB for M2F Master / Slave 1 / Slave 2
Replace the fan PCB. (
1)
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Is the
connector of
relevant fan motor
normally connected?
(
1)
Resistance
between U, V, W
phases of the fan motor
power supply cable has lost
balance or short circuit is
caused between U,
V, W phases.
Turn OFF the power supply
and wait for 10 minutes.
Fan motor
Fan PCB
Connector
M1F
A6P
X1A
M2F
A5P
X1A
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...