SiUS342004EB
Troubleshooting by Error Code
Part 6 Service Diagnosis
300
3.43 Harness Abnormality (between Outdoor Unit Main PCB
and Inverter PCB)
Applicable
Models
All outdoor unit models
Error Code
H3
Method of Error
Detection
Check for the transmission conditions of the harnesses between the PCBs using microcomputer.
Error Decision
Conditions
Normal transmission between the PCBs is disabled while the compressor is not running.
Supposed
Causes
Defective connection of jumpers between PCB
Defective outdoor unit main PCB (A1P)
Defective inverter PCB
Troubleshooting
Check for the transmission
conditions of the following
harnesses.
(1) X6A (Inverter PCB)
↔
X28A (A1P)
(2) X63A (Inverter PCB)
↔
X40A (A1P)
Replace the outdoor unit main
PCB (A1P).
Replace the inverter PCB (A4P).
YES
NO
YES
Complete countermeasures.
Return the relevant harness to
normal.
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Harness error
H3
error recurs.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...