SiUS342004EB
Troubleshooting by Error Code
Part 6 Service Diagnosis
270
3.24 Combination Error between Indoor Unit Control PCB and
Fan PCB
Applicable
Models
FXSQ-TA, FXSQ-TB, FXMQ-PB, FXMQ-TB, FXMQ-TA
Error Code
C6
Method of Error
Detection
Check the condition of transmission with fan PCB (A2P) using indoor unit control PCB (A1P).
Error Decision
Conditions
When the communication data of fan PCB (A2P) is determined as incorrect.
Supposed
Causes
Defective fan PCB (A2P)
Defective connection of capacity setting adaptor
Field setting error
Troubleshooting
N
O
Caution
Be sure to turn off the po
w
er s
w
itch before connecting or disconnecting
connectors, or parts may be damaged.
W
as
indoor unit
control PCB
(A1P) replaced
w
ith a spare
PCB?
YES
YES
YES
N
O
N
O
W
as
correct
capacity setting
adaptor installed
w
hen replacing it
w
ith a spare
PCB?
After establishing transmission
for indoor and outdoor units,
diagnose the operation again.
After establishing transmission
for indoor and outdoor units,
diagnose the operation again.
Replace it
w
ith correct fan PCB
(A2P).
Install correct capacity setting
adaptor.
Does
the fan PCB
part
N
o. match that
of the spare
parts list?
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...