SiUS342004EB
Troubleshooting by Error Code
Part 6 Service Diagnosis
242
3.8 Overload/Overcurrent/Lock of Indoor Fan Motor
Applicable
Models
FXMQ-M
Error Code
A6
Outline
This error is detected by detecting that the individual power supply for the fan turns OFF.
Error Decision
Conditions
When it is not detected that the individual power supply for the indoor fan turns ON while in
operation.
Supposed
Causes
Defective power supply for the indoor fan motor
Clogged drain piping
Activation of the indoor unit safety device
Defective contact in the fan wiring circuit
Troubleshooting
Properly connect the ca
b
le.
NO
YES
YES
Is the
power s
u
pply
ca
b
le of the indoor fan
properly
connected?
NO
Is the fan
normally r
u
nning?
Restart the fan.
Replace the indoor
u
nit control
PCB (A1P).
It is s
u
pposed that the indoor
fan motor (M1F, M2F) stops
r
u
nning d
u
e to o
v
erload,
o
v
erc
u
rrent, or lock.
Caution
Be s
u
re to t
u
rn off the power switch
b
efore connecting or disconnecting
connectors, or parts may
b
e damaged.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...