Troubleshooting by Error Code
SiUS342004EB
217
Part 6 Service Diagnosis
3. Troubleshooting by Error Code
3.1 Error Codes and Descriptions
k
: ON
h
: OFF
l
: Blink
Error
code
Operation
lamp
Error contents
Reference
page
Indoor
Unit
A0
l
External protection device abnormality
A1
l
Indoor unit control PCB abnormality
A3
l
Drain level control system abnormality
A6
l
Indoor fan motor lock, overload
Indoor fan motor abnormality
Overload/overcurrent/lock of indoor fan motor
Blower motor not running
Indoor fan motor status abnormality
Low indoor airflow
A7 (
1)
k
Swing flap motor abnormality
A8
l
Power supply voltage abnormality
Blower motor stops for over/under voltage
A9
l
Electronic expansion valve coil abnormality, dust clogging
AA
l
Gas furnace abnormality
AF (
1)
k
Drain level above limit
AH
l
Self-cleaning decoration panel abnormality
AJ
l
Defective capacity setting
C1
l
Transmission abnormality between indoor unit control PCB and fan PCB
Blower motor communication error
Climate Talk communication error
C4
l
Indoor heat exchanger liquid pipe thermistor abnormality
C5
l
Indoor heat exchanger gas pipe thermistor abnormality
C6
l
Combination error between indoor unit control PCB and fan PCB
Capacity setting abnormality
Blower motor HP mismatch
Indoor blower does not have required parameters to function
C9 (
2)
l
Suction air thermistor abnormality
Remote sensor abnormality
CA
l
Discharge air thermistor abnormality
CE (
1)
k
Infrared presence/floor sensor error
CJ (
2)
k
Remote controller thermistor abnormality
Outdoor
Unit
E1
l
Outdoor unit main PCB abnormality
E2
l
Detection of ground leakage by leak detection circuit
Missing of ground leakage detection core
E3
l
Activation of high pressure switch
E4
l
Activation of low pressure sensor
E5
l
Compressor motor lock
E6
l
Compressor damage alarm
E7
l
Outdoor fan motor abnormality
E9
l
Electronic expansion valve coil abnormality
F3
l
Discharge pipe temperature abnormality
F4
k
/
Kl
Wet alarm
F6
l
Refrigerant overcharged
H3
l
Harness abnormality (between outdoor unit main PCB and inverter PCB)
H7
l
Outdoor fan PCB abnormality
H9
l
Outdoor air thermistor (R1T) abnormality
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...