Field Settings for Outdoor Unit
Part 5 Field Settings and Test Operation
188
Note(s)
1. Indoor condition A: Temperature difference Average of (indoor air temperature – set
temperature) is less than 1.5°C (2.7°F).
2. Indoor condition B: Temperature difference Average of (indoor air temperature – set
temperature) is 3°C (5.4°F) or more.
[2-32]:
Forced, all time, power consumption limitation operation (no external control adaptor
is required to perform power consumption limitation)
If the system always needs to run under power consumption limitation conditions,
this setting activates and defines the level power consumption limitation that will be
applied continuously. The level is according to the table.
Default value: 0 (OFF).
Value
[2-32]
Restriction reference
0 (default)
Function not active
1
Follows [2-30] setting
2
Follows [2-31] setting
Change [2-32]: 0,1 or 2 in function of required limitation.
[2-34]:
Indoor fan tap setting
Indoor units fan speed limitation related to connection capacity and outdoor air
temperature for energy saving
Value
[2-34]
Indoor fan tap setting
0 (default)
Fan speed is limited to L tap when indoor units capacity
130%.
1
In heating mode, fan speed is limited to L tap when indoor units capacity
130%.
2
Fan speed follows the setting of remote controllers (not limited by indoor units
connection capacity).
3
Limited in cooling when Ta < 29.5°C (85.1°F) and Indoor condition is in condition A
(
1)
Returned when Ta > 32.5°C (90.5°F) or Indoor condition is in condition B (
2)
4
Limited in cooling when Ta < 23.5°C (74.3°F) and Indoor condition is in condition A
(
1)
Returned when Ta > 26.5°C (79.7°F) or Indoor condition is in condition B (
2)
5
Limited in cooling when Ta < 19.3°C (66.7°F) and Indoor condition is in condition A
(
1)
Returned when Ta > 22.3°C (72.1°F) or Indoor condition is in condition B (
2)
6
Limited in cooling when Ta < 29.5°C (85.1°F)
Returned when Ta > 32.5°C (90.5°F)
7
Limited in cooling when Ta < 23.5°C (74.3°F)
Returned when Ta > 26.5°C (79.7°F)
8
Limited in cooling when Ta < 19.3°C (66.7°F)
Returned when Ta > 22.3°C (72.1°F)
[2-35]:
Height difference setting
Default value: 1
In case the outdoor unit is installed in the lowest position (indoor units are installed
on a higher position than outdoor units) and the height difference between the
highest indoor unit and the outdoor unit exceeds 40 m (130 ft), the setting [2-35]
should be changed to 0.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...