SiUS342004EB
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
156
Note(s)
Note(s)
1.3.21 Airflow Setting when Cooling Thermostat is OFF
This is used to set airflow to LL airflow when cooling thermostat is OFF.
If the airflow setting when thermostat is OFF is set to 03: OFF, the air in the indoor unit will be
stagnant and suction air thermistor may not detect room temperature correctly, resulting in
problems that thermostat will not be ON easily.
Use optional remote sensor in such conditions, or set the field setting 10 (20)-2 to
03
(only remote
controller thermistor).
: Factory setting
1.3.22 Ceiling Height Setting, Setting of Normal Airflow
Make the following setting according to the ceiling height. The second code No. is set to
01
at the
factory.
1. The Second Code No. is factory set to Standard/All round outlet. For High ceiling (1) or (2),
initial setting by remote controller is required.
2. A closing member kit (optional) is required for 4-, 3-, or 2-direction airflow.
1. The Second Code No. is factory set to Standard/All round outlet. For High ceiling (1) or (2),
initial setting by remote controller is required.
2. A closing member kit (optional) is required for 4-, 3-, or 2-direction airflow.
Mode
No.
First Code
No.
Second Code
No.
Contents
12 (22)
6
01
LL tap
02
Set fan speed
03
OFF
FXFQ07-24AA, FXFQ07-24T
: Factory setting
Mode
No.
First
Code
No.
Second
Code No.
Setting
Ceiling Height
All round outlet
4-way outlets
3-way outlets
2-way outlets
13
(23)
0
01
Standard
Lower than
2.7 m
(8-3/4 ft)
Lower than
3.1 m
(10-1/8 ft)
Lower than
3.0 m
(10 ft)
Lower than
3.5 m
(11-1/2 ft)
02
High
Ceiling (1)
Lower than
3.0 m
(10 ft)
Lower than
3.4 m
(11-1/8 ft)
Lower than
3.3 m
(10-3/4 ft)
Lower than
3.8 m
(12-1/2 ft)
03
High
Ceiling (2)
Lower than
3.5 m
(11-1/2 ft)
Lower than
4.0 m
(13-1/8 ft)
Lower than
3.5 m
(11-1/2 ft)
—
FXFQ30-54AA, FXFQ30-48T
: Factory setting
Mode
No.
First
Code
No.
Second
Code No.
Setting
Ceiling Height
All round outlet
4-way outlets
3-way outlets
2-way outlets
13
(23)
0
01
Standard
Lower than
3.2 m
(10-1/2 ft)
Lower than
3.4 m
(11-1/8 ft)
Lower than
3.6 m
(12 ft)
Lower than
4.2 m
(13-3/4 ft)
02
High
Ceiling (1)
Lower than
3.6 m
(12 ft)
Lower than
3.9 m
(12-3/4 ft)
Lower than
4.0 m
(13-1/8 ft)
Lower than
4.2 m
(13-3/4 ft)
03
High
Ceiling (2)
Lower than
4.2 m
(13-3/4 ft)
Lower than
4.5 m
(14-3/4 ft)
Lower than
4.2 m
(13-3/4 ft)
—
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...