Outline of Control (Indoor Unit)
SiUS342004EB
105
Part 4 Functions and Control
9. Outline of Control (Indoor Unit)
Regarding the outline of control for low-temperature hydrobox (HXY-TA), refer to the service
manual SiUS392016EA.
9.1 Operation Flowchart
Is
test run in
progress?
Is freeze-
up prevention operation in
progress?
Is
Restart prevention
operation in progress?
(5 min.)
Dew
prevention condition?
Is the safety
device activated?
Start
Heating Operation
Fan Operation
Cooling Operation
Cooling Operation
Detect louver lock
( )
Run or Stop?
RUN indicating lamp: OFF
RUN indicating lamp: Blink
Error code: Displayed
RUN indicating lamp: OFF
Error mode display: Reset
Thermostat status
Swing flap
Swing flap
Set wind direction
Program dry display: Reset
Program dry operation
A
A
A
Stop
Run
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
ON
OFF
No
No
No
1
Fan
Temp. control
Heating
Cooling
2 Fan : Stop
Louver : Stop
3
4
7
4
6
5
(Option)
OFF
ON
MF
MF
: OFF
MP
Drain pump kit
MP
Drain pump kit
MP
Drain pump kit
:ON
MP
Drain pump kit
: ON
MP
: Closed
Electronic expansion valve
: Capacity control
Electronic expansion valve
: Closed
YE
MA
: OFF
EH
: OFF
EH
Humidifier : OFF
Hu
Humidifier : OFF
Hu
YE
The previous settings of airflow
rate, wind direction, and
temperature are displayed.
Is the RUN
indicating lamp
blinking?
Press the RESET
RUN/STOP push
button.
Electronic
expansion valve
Thermostat-ON-
operation signal to
outdoor unit: Output
Thermostat-ON-
operation signal to
outdoor unit: Output
RUN indicating lamp: ON
Airflow rate display: Displayed
Wind direction display: Displayed
Temp. setting display: Displayed
Turn ON
power supply
Initialize electronic
expansion valve
LED in remote
controller turns ON
Cyclic operation with
RUN/STOP push button
Fan or Temp.
control?
Cooling or
Heating?
Drain
pump kit
Aux. electric
heater
Aux. electric
heater
Dew prevention position
Cassette type: P1
Ceiling suspended type: P0
Program dry
ON/OFF
Fan:
Operating with set airflow rate
: OFF after 5-min.
residual operation
: OFF after 5-min.
residual operation
Yes
YE
YE
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...