2
|
Troubleshooting
Service manual
87
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.66 J5-18-19-20 – Suction temperature thermistor R10T abnormality
Main error code
Sub error code
Unit
J5
18
Main
19
Sub 1
20
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Thermistor read-out is out
of range
Unit will stop operating.
Auto-reset when
thermistor read-out is
within range
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform
a
check
of
the
suction
pipe
thermistor.
See
348].
Possible cause:
Faulty suction pipe thermistor or connector fault.
2
Perform a check of the Sub PCB. See
342].
Possible cause:
Faulty Sub PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.67 J6-01-02-03 – De–icer thermistor R11T abnormality
Main error code
Sub error code
Unit
J6
01
Main
02
Sub 1
03
Sub 2