2
|
Troubleshooting
Service manual
77
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
1
Perform a check of the outdoor unit fan motor M2F. See
307].
Possible cause:
Faulty outdoor unit fan motor M2F.
2
Perform a check of the fan inverter PCB A7P. See
Possible cause:
Faulty fan inverter PCB A7P.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.53 H7-21-23-25 – Defective fan inverter PCB A7P
Main error code
Sub error code
Unit
H7
01
Main
05
Sub 1
09
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Abnormal current form
detected by fan inverter
PCB during start-up of fan
motor.
Unit will stop operating.
Power reset at outdoor
unit.
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the outdoor unit fan motor M2F. See
307].
Possible cause:
Faulty outdoor unit fan motor M2F.
2
Perform a check of the fan inverter PCB A7P. See
Possible cause:
Faulty fan inverter PCB A7P.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.