2.3.44 F6-02 – Refrigerant overcharge detection during test-run
Trigger
Effect
Reset
Discharge superheat
<10˚C (SH
Discharge
=T
Discharge
−
T
condensation
) during test run.
Unit will stop test run.
Push BS3 (return) button
once.
Excessive subcool is
detected from
comparison of R1T
ambient thermistor, R3T
liquid thermistor, R11T
de-icer thermistor to
saturated temperature
derived from high
pressure sensor S1NPH.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the outdoor air thermistor. See
348].
Possible cause:
Faulty ambient air thermistor.
2
Perform a check of the main refrigerant liquid thermistor. See
348].
Possible cause:
Faulty main refrigerant liquid thermistor or connector fault.
3
Perform a check of the de–icer thermistor. See
348].
Possible cause:
Faulty de–icer thermistor or connector fault.
4
Check if the refrigerant circuit is correctly charged. See
Possible cause:
Refrigerant overcharge.
5
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
363].
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
6
Perform a check of the evaporator side expansion valve. See
Possible cause:
Faulty evaporator side expansion valve.
7
Check for objects near the indoor unit that may block the airflow. See
372].
Possible cause:
Airflow of the indoor unit is blocked.
8
Clean the air filters of the indoor unit(s). See service manual of the respective
indoor unit(s).
Possible cause:
Faulty or clogged air filter.
9
Adjust external static pressure setting for ducted type indoor units, if
necessary.
10
Perform a check of the indoor unit fan motor. See service manual of the
respective indoor unit(s).