3
|
Components
Service manual
311
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
c
b
d
a
e
a
Screw
b
Allen key
c
Axle cover
d
Propeller fan blade assembly
Is the problem solved?
Action
Yes
No further actions required.
No
Return to
307] of the outdoor unit
fan motor and continue with the next
procedure.
3.14.2 Double fan outdoor unit
INFORMATION
See
441] for the correct location of DC fan motors M1F
and M2F.
Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a mechanical check of the propeller fan blade assemblies
Prerequisite:
Stop the unit operation via the central controller.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
If propeller fan blade touches the bellmounth, check if the fan motor is
correctly mounted on its base, see
2
Check the state of the propeller fan blade assemblies for damage,
deformations and cracks.
One or both propeller fan blade
assemblies are damaged?
Action
Yes
Replace the damaged propeller fan
blade assembly, see
313].