Troubleshooting
Service manual
23
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the main PCB. See
290].
Possible cause:
Faulty main PCB.
2
Check if the power supply is conform with the regulations. See
Possible cause:
▪
Faulty or disturbance of the power supply (imbalance >10%),
▪
Power drop,
▪
Short circuit.
3
Check the F1‑F2 transmission line between the indoor units and outdoor unit.
See
Possible cause:
Faulty or interruption in transmission line between indoor
units and outdoor unit.
4
Perform a power reset. If the error disappears and is raised again after a
while, check for the presence of an external source causing electrical noise.
See
Possible cause:
External source may cause interference.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.3 E1-02 – Outdoor unit main PCB A1P error
Trigger
Effect
Reset
Defected main PCB.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
1
Perform a check of the main PCB. See
290].
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.4 E2-01-02-03 – Current leak detection
Main error code
Sub error code
Unit
E2
01
Main
02
Sub 1
03
Sub 2