2
|
Troubleshooting
Service manual
181
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
To solve the error code
1
Check dip switch settings for multi branch selector boxes.
Possible cause:
Wrong dipswitch setting.
2
Apply correct dip switch setting while branch selector box power is OFF. After
correcting the dip switch, turn on the power and perform a communication
reset on the outdoor unit PCB. See
"How to perform a communication
362].
3
Check all indoor unit connection to the branch selector box. Correct any
wiring or piping fault.
Possible cause:
Piping and/or wiring fault of indoor units to branch selector
box.
4
Check power supply to all indoor units. Turn on any indoor unit where power
is OFF. After Indoor unit(s) power ON, perform a communication reset on
outdoor unit PCB. See
"How to perform a communication reset"
Possible cause:
Indoor unit(s) with power OFF.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.193 UF-01 – Wiring and piping mismatch - Auto address inconsistency on F1-F2 transmission
Trigger
Effect
Reset
Minimum 1 indoor unit
fails to perform cross pipe
check during test run.
Forced stop.
Perform test run.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check that all stop valves of the refrigerant circuit are open. See
Possible cause:
Closed stop valve in the refrigerant circuit.
2
Check that the refrigerant circuit piping and wiring connections of the system
are correctly installed.
Possible cause:
Refrigerant piping and/or wiring mismatch.
3
Set field setting 2‑5 of the outdoor unit to 1 to start the indoor units
connected to that outdoor unit on forced fan operation, see
455]. If any of these indoor units is NOT operating, check the
indoor unit(s) that have power black‑out or malfunctioning PCB. See service
manual of the respective indoor unit for more information.
Possible cause:
Power black‑out or malfunctioning PCB on indoor unit(s).
4
Check field setting 1‑10 to count the indoor units, see
455]. If less indoor units detected than it should be, check the
indoor unit(s) that have power black‑out or malfunctioning PCB. See service
manual of the respective indoor unit for more information.