Troubleshooting
Service manual
123
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
2.3.108 L9-01-05-06 – Stall prevention by inverter PCB A3P
Main error code
Sub error code
Unit
L9
01
Main
05
Sub 1
06
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Inverter PCB A3P detects
overcurrent or no rotation
at start-up.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check if the power supply is conform with the regulations. See
Possible cause:
▪
Faulty or disturbance of the power supply (imbalance >10%),
▪
Power drop,
▪
Short circuit.
2
Check if the refrigerant circuit is clogged. See
Possible cause:
Clogged refrigerant circuit.
3
Perform a check of the inverter PCB A3P. See
Possible cause:
Faulty inverter PCB A3P.
4
Perform a check of the compressor M1C. See
221].
Possible cause:
Faulty compressor M1C.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.109 L9-10-11-12 – Stall prevention by inverter PCB A6P
Main error code
Sub error code
Unit
L9
10
Main
11
Sub 1
12
Sub 2