![Daikin VRV IV W+ Series Installer And User Reference Manual Download Page 50](http://html.mh-extra.com/html/daikin/vrv-iv-w-series/vrv-iv-w-series_installer-and-user-reference-manual_2459209050.webp)
15
|
About the box
Installer and user reference guide
50
RWEYQ8~14T9Y1B
VRV IV water-cooled system air conditioner
4P452191-1B – 2020.10
Accessory pipes (mm)
HP
Øa
Øb
Øc
Ød
High pressure/Low
pressure gas pipe
▪
Front connection
(a)
Øa
Øb
▪
Top connection
Øc
Ød
8
25.4
25.4
25.4
15.9
10
19.1
12
14
22.2
(a) Braze the straight accessory pipe onto the L-shaped accessory pipe in order to get
the correct diameter to connect the field pipes (for front connection).
15.6 To remove the transportation stay
NOTICE
If the unit is operated with the transportation stay attached, abnormal vibration or
noise may be generated.
The compressor transportation stay must be removed. It is installed under the
compressor leg in order to protect the unit during transport. Proceed as shown in
the figure and procedure below.
1
Remove the bolt.
2
Lift the insulation to access the compressor mounting bolt.
3
Slightly loosen the mounting bolt.
4
Remove the transportation stay as shown in the figure below.
5
Tighten the mounting bolt to 12.3 N•m of torque.
1
3
5
(12.3 N·m)
2