SiUS331604E
Field Setting from Remote Controller
Field Setting
80
2. Field Setting from Remote Controller
Individual function of indoor unit can be changed from the remote controller. At the time of installation or after
service inspection / repair, make the local setting in accordance with the following description.
Wrong setting may cause error.
(When an optional accessory is installed on the indoor unit, settings for the indoor unit may need to be changed.)
2.1
Wired Remote Controller — BRC1E73
,
,
<Basic screen>
(1)
<Service Settings menu screen>
(2)
Press Menu/OK button.
<Service Settings screen>
(3)
(4)
(5)
(3)
(5)
Press Menu/OK button.
FIRST CODE (SW) NO.
SECOND CODE NO.
Press and hold Cancel
button for 4 seconds or
more during backlight lit.
In the case of individual
setting per indoor unit
In the case of group total
setting
1.
Press and hold Cancel button for
4 seconds or more.
Service settings menu is
displayed.
2.
Select
Field Settings
in the
Service Settings menu, and
press Menu/OK button.
Field settings screen is
displayed.
3.
Highlight the mode, and select
desired “Mode No.” by using
(Up/Down) button.
4.
In the case of setting per indoor
unit during group control (When
Mode No. such as
20
,
21
,
22
,
23
,
25
are selected),
highlight the unit No. and select
“Indoor unit No.” to be set by
using (Up/Down) button.
(In the case of group total setting,
this operation is not needed.)
In the case of individual setting
per indoor unit, current settings
are displayed. And, SECOND
CODE NO. “ - ” means no
function.
5.
Highlight SECOND CODE NO. of
the FIRST CODE NO. to be
changed, and select desired
“SECOND CODE NO.” by using
(Up/Down) button. Multiple
identical mode number settings
are available.
In case of setting for all indoor
units in the remote control
group, available SECOND
CODE NO. is displayed as “
∗
”
which means it can be
changed.
When SECOND CODE NO. is
displayed as “ - ”, there is no
function.
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...