SiUS331604E
Servicing Items to be Confirmed
Service Diagnosis
120
(5) Precautions for operating in servicing mode (field setting):
When a test operation is interrupted or after exiting service mode, please wait for at least one minute before entering
service mode again. In case of continuous execution, the outdoor unit PCB may sometimes display an error code. If any
error codes are displayed, press the
RETURN
button (BS3). If performing the above operation still does not eliminate
the error, reconnect the unit to the power supply.
1.3
Refrigerant Properties (R-410A)
Temperature
Absolute
Pressure
Temperature
Absolute
Pressure
Temperature
Absolute
Pressure
Temperature
Absolute
Pressure
°C
°F
MPa
psi
°C
°F
MPa
psi
°C
°F
MPa
psi
°C
°F
MPa
psi
–50
–58
0.11
16.0
–20
–4
0.40
58.0
10
50.0
1.09
158
40
104.0
2.42
351
–48
–54.4
0.12
17.4
–18
–0.4
0.43
62.4
12
53.6
1.15
167
42
107.6
2.54
368
–46
–50.8
0.13
18.9
–16
3.2
0.46
66.7
14
57.2
1.22
177
44
111.2
2.67
387
–44
–47.2
0.15
21.8
–14
6.8
0.50
72.5
16
60.8
1.29
187
46
114.8
2.80
406
–42
–43.6
0.16
23.2
–12
10.4
0.54
78.3
18
64.4
1.37
199
48
118.4
2.93
425
–40
–40
0.18
26.1
–10
14
0.57
82.7
20
68.0
1.45
210
50
122.0
3.07
445
–38
–36.4
0.19
27.6
–8
17.6
0.61
88.5
22
71.6
1.53
222
52
125.6
3.21
466
–36
–32.8
0.21
30.5
–6
21.2
0.66
95.7
24
75.2
1.61
234
54
129.2
3.36
487
–34
–29.2
0.23
33.4
–4
24.8
0.70
102
26
78.8
1.70
247
56
132.8
3.51
509
–32
–25.6
0.25
36.3
–2
28.4
0.75
109
28
82.4
1.79
260
58
136.4
3.64
528
–30
–22
0.27
39.2
0
32
0.80
116
30
86.0
1.89
274
60
140.0
3.83
555
–28
–18.4
0.29
42.1
2
35.6
0.85
123
32
89.6
1.99
289
62
143.6
4.00
580
–26
–14.8
0.32
46.4
4
39.2
0.91
132
34
93.2
2.09
303
64
147.2
4.17
605
–24
–11.2
0.34
49.3
6
42.8
0.96
139
36
96.8
2.20
319
–22
–7.6
0.37
53.7
8
46.4
1.02
148
38
100.4
2.31
335
4.0
3.8
3.6
3.4
3.2
3.0
2.8
2.6
2.4
2.2
2.0
1.8
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
0.0
3.9
3.7
3.5
3.3
3.1
2.9
2.7
2.5
2.3
2.1
1.9
1.7
1.5
1.3
1.1
0.9
0.7
0.5
0.3
0.1
–0.1
0
–10
–20
–30
–40
–50
10
20
30
40
50
60
32
14
–4
–22
–40
–58
50
68
86
104
122
140
Temperature
Absolute pressure
Pressure
g
au
g
e v
alue
MPa
psi
psi G
MPa G
˚C
˚F
580
551
522
493
464
435
406
377
348
319
290
261
232
203
174
145
116
87
58
29
0
566
537
508
479
450
421
392
363
334
305
276
247
218
189
160
131
102
73
44
15
–15
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...