Field Setting from Outdoor Unit
SiUS331604E
109
Field Setting
3.6
Setting of Low Noise Operation and Demand Operation
Setting of Low Noise Operation
By connecting the external contact input to the low noise input of the external control adaptor for outdoor unit
(optional), you can lower operating noise by 2-3 dB.
When the low noise operation is automatically carried out at night (The external control adaptor for
outdoor unit is not required)
1. While in setting mode 2, select the setting condition (i.e., Mode 1, Mode 2, or Mode 3) for set item No. 22
(Setting of night-time low noise level).
2. If necessary, while in setting mode 2, select the setting condition (i.e., 20:00, 22:00, or 24:00) for set item No.
26 (Setting of start time of night-time low noise operation).
(Use the start time as a guide since it is estimated according to outdoor temperatures.)
3. If necessary, while in setting mode 2, select the setting condition (i.e., 06:00, 07:00, or 08:00) for set item No.
27 (Setting of end time of night-time low noise operation).
(Use the end time as a guide since it is estimated according to outdoor temperatures.)
4. If necessary, while in setting mode 2, set the setting condition for set item No. 29 (Setting of capacity
precedence) to ON.
(If the condition is set to ON, when the air-conditioning load reaches a high level, the system enters to normal
operation mode even during nighttime.)
Image of operation
Operation sound
Rated operation
sound
Operation sound
of mode 1
Operation sound
of mode 2
Operation sound
of mode 3
Time set with night-time low noise start setting
If capacity precedence is set in capacity
precedence setting, the fan speed will be
increased according to the load of air
conditioning when load is heavier.
Night time
Time set with night-time low noise end setting
Operation sound during
night-time low noise mode
is instructed can be set with
night-time low noise level
setting.
(Factory setting is OFF.)
Operation sound level set with
night-time low noise setting
Set with night-time low noise start setting.
(Factory setting is PM 10:00.)
Set with night-time low noise end setting.
(Factory setting is AM 8:00.)
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...