19
|
Configuration
Installer and user reference guide
110
R R8T7V1B
VRV IV heat pump for indoor installation
4P499898-1A – 2020.10
7‑LEDs display or 7-segments display
The display gives feedback about the field settings, which are defined as [Mode-
Setting]=Value.
The display differs depending on the model.
Model
Display
5 HP
7‑LEDs display:
▪
H1P: Shows the mode
▪
H2P~H7P: Shows the settings and values, represented in
binary code
(H8P: NOT used for field settings, but used during
initialisation)
8 HP
7‑segments display (
)
Example:
H1P H2P H3P H4P H5P H6P H7P
-
+
+
+
+
+
[
H1P
32 16
8
4
2
1]
Description
(H1P OFF)
Default situation
(H1P flashing)
Mode 1
(H1P ON)
Mode 2
+
+
+
+
+
0
0
8
0
0
0
(H2P~H7P = binary 8)
Setting 8
(in mode 2)
+
+
+
+
+
0
0
0
4
0
0
(H2P~H7P = binary 4)
Value 4
(in mode 2)
19.2.4 To access mode 1 or 2
After the units are turned ON, the display goes to its default situation. From there,
you can access mode 1 and mode 2.
Initialisation: default situation
NOTICE
Be sure to turn ON the power 6 hours before operation in order to have power
running to the crankcase heater and to protect the compressor.
Turn on the power supply of the compressor unit, heat exchanger unit, and all
indoor units. When the communication between the compressor unit, heat
exchanger unit, and indoor units is established and normal, the display indication
state will be as below (default situation when shipped from factory).