18
|
Electrical installation
Installer and user reference guide
105
R R8T7V1B
VRV IV heat pump for indoor installation
4P499898-1A – 2020.10
18.5 To close the compressor unit
NOTICE
When closing the cover, make sure that the tightening torque does NOT exceed
4.1 N•m.
2
1
4×
SW8
5×
SW8
18.6 To close the heat exchanger unit
NOTICE
When closing the cover, make sure that the tightening torque does NOT exceed
4.1 N•m.
2×
SW8
18.7 To check the insulation resistance of the compressor
NOTICE
If, after installation, refrigerant accumulates in the compressor, the insulation
resistance over the poles can drop, but if it is at least 1 MΩ, then the unit will not
break down.
▪
Use a 500 V mega-tester when measuring insulation.
▪
Do NOT use a mega-tester for low voltage circuits.
1
Measure the insulation resistance over the poles.