Troubleshooting (OP: Unified ON/OFF Controller)
Si37-701
352
Troubleshooting
[CHECK 7] Broken Wire Check of the Connecting Wires
1. Procedure for checking outdoor-outdoor unit transmission wiring for broken wires
On the system shown below, turn OFF the power supply to all equipment, short-circuit
between the outdoor-outdoor unit terminal parts F1 and F2 in the "Outdoor Unit A" that is
farthest from the central remote controller, and then conduct continuity checks between the
transmission wiring terminal blocks F1 and F2 of the central remote controller using a
multiple meter. If there is continuity between the said terminal blocks, the outdoor-outdoor
unit transmission wiring has no broken wires in it.
If there is no continuity, the transmission wiring may have broken wires. With the outdoor-
outdoor unit terminal parts of the "Outdoor Unit A" short-circuited, conduct continuity checks
between the transmission wiring terminal blocks F1 and F2 of the unified ON/OFF controller.
If there is no continuity as well, conduct continuity checks between the outdoor-outdoor unit
terminal parts of the "Outdoor Unit E", between the outdoor-outdoor unit terminal parts of the
"Outdoor Unit D", between the outdoor-outdoor unit terminal parts of the "Outdoor Unit C", …
in the order described, thus identifying the place with continuity.
If the place with continuity can be identified, there may be broken wires in places before the
said place with continuity.
2. Procedure for checking indoor-outdoor unit transmission wiring for broken wires (for
checking the indoor-outdoor unit transmission wiring of the "Outdoor Unit C" for broken
wires)
Turn OFF the power supply to all equipment, short-circuit between the indoor-outdoor unit
terminal parts F1 and F2 in the "Outdoor Unit C, and then conduct continuity checks
between the transmission wirings F1 and F2 of the "Indoor Unit a" that is farthest from the
"Outdoor Unit C" using a multiple meter. If there is continuity between the said transmission
wirings, the indoor-outdoor unit transmission wiring has no broken wires in it.
If there is no continuity, the transmission wiring may have broken wires. With the indoor-
outdoor unit terminal parts of the "Outdoor Unit C" short-circuited, identify the place with
continuity in the transmission wiring of the "Indoor Unit b", transmission wiring of the "Indoor
Unit c", and transmission wiring of the "Indoor Unit d" in the order described.
If the place with continuity can be identified, there may be broken wires in places before the
said place with continuity.
Short-circuit
between the
outdoor-outdoor
unit terminal
parts.
Outdoor-outdoor Unit
Transmission Wiring
Check the transmission
wiring for continuity.
If there is continuity, the
indoor-outdoor unit
transmission has no
broken wires in it.
Indoor-outdoor Unit
Transmission Wiring
Short-circuit between
the indoor-outdoor unit
terminal parts.
Check the transmission
wiring for continuity.
If there is continuity, the
outdoor-outdoor unit
transmission has no broken
wires in it.
Unified ON/OFF controller
Central remote controller
Summary of Contents for VRV III REYQ8PY1
Page 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701...
Page 59: ...Specifications Si37 701 48 Specifications...
Page 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit...
Page 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219...
Page 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH...
Page 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743...
Page 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742...
Page 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741...
Page 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A...
Page 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C...
Page 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E...
Page 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E...
Page 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E...
Page 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359...
Page 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1...
Page 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B...
Page 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C...
Page 423: ...Piping Installation Point Si37 701 412 Appendix...
Page 427: ...Example of Connection R 410A Type Si37 701 416 Appendix...
Page 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix...
Page 447: ...Si37 701 iv Index...
Page 451: ...Si37 701 viii Drawings Flow Charts...