Field Setting
Si37-701
204
Test Operation
3.2.9 Emergency Operation
If any of the compressors goes wrong, disable the relevant compressor or the relevant outdoor
unit from operating, and then conduct emergency operation only with operational compressors
or outdoor units.
There are two ways of conducting the Emergency operation :
with remote controller reset and
by setting outdoor unit PC board.
Emergency operation with remote controller reset
On the multi outdoor unit system, if any of the outdoor unit line causes a malfunction (in this
case, the system will stop and the relevant malfunction code will be displayed on the indoor
remote controller), disable only the relevant outdoor unit from operating for a 8 hours using
the indoor remote controller, and then conduct emergency operation with operational
outdoor units.
[Emergency operation method]
•
Reset the remote controller (i.e., press the RUN/STOP button on the remote controller for 4
seconds or more) when the outdoor unit stops because of malfunction state.
[Details of operation]
•
Automatically disable the defective outdoor unit from operating, and then operate other
outdoor units.
•
The following section shows malfunction codes on which this emergency operation is
possible.
*1: When malfunction codes E7 and H7 are shown, the
possibility of emergency operation is decided as
follows.
While in heating or cooling-heating concurrent
operation
• One out of three connected outdoor units
malfunctions.
→
Emergency operation is
possible.
• Two out of three connected outdoor units
malfunction.
→
Emergency operation is not
possible.
• One out of two connected outdoor units
malfunctions.
→
Emergency operation is not
possible.
Emergency operation by setting outdoor unit PC board
In malfunction stop state of the outdoor unit due to defective compressor, by setting the
relevant compressor or relevant outdoor unit to "Disabling operation setting", the emergency
operation is conducted with operational compressors or outdoor units.
<REYQ8 to 16PY1>
8
Disabling the compressor 1 (on the right side) from operating:
Set No. 38 of setting mode 2 to "Disable-compressor-1 operation".
Operating method
Applicable model
Emergency operation with
remote controller reset
(Auto backup operation)
Emergency operation with
outdoor unit PC board setting
(Manual backup operation)
REYQ8 to 16PY1
–
Backup operation by the
compressor
REYQ18 to 48PY1
Backup operation by the
indoor unit
Backup operation by the
outdoor unit
LED display (
8
: ON,
1
: OFF,
9
: Blink)
(Step)
H1P-----------H7P
(1) Press and hold the PAGE button (BS1)
for 5 sec. or more.
8111111
(2) Press the OPERATE button (BS2) 38
times.
8811881
(3) Press the CHECK button (BS3) once.
8111119
(Factory setting)
(4) Press the OPERATE button (BS2) once.
8111191
(5) Press the CHECK button (BS3) twice.
8111111
(6) Press the PAGE button (BS1) once.
1181111
E3, E4, E5, E7 (*1)
F3
H7 (*1), H9
J2, J3, J5, J6, J7, J9, JA, JC
L3, L4, L5, L8, L9, LC
U2, UJ
Summary of Contents for VRV III REYQ8PY1
Page 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701...
Page 59: ...Specifications Si37 701 48 Specifications...
Page 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit...
Page 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219...
Page 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH...
Page 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743...
Page 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742...
Page 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741...
Page 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A...
Page 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C...
Page 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E...
Page 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E...
Page 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E...
Page 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359...
Page 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1...
Page 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B...
Page 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C...
Page 423: ...Piping Installation Point Si37 701 412 Appendix...
Page 427: ...Example of Connection R 410A Type Si37 701 416 Appendix...
Page 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix...
Page 447: ...Si37 701 iv Index...
Page 451: ...Si37 701 viii Drawings Flow Charts...