Field Setting
Si37-701
202
Test Operation
Detailed Setting Procedure of Low Noise Operation and Demand Control
1. Setting mode 1 (H1P off)
c
In setting mode 2, push the BS1 (MODE button) one time.
→
Setting mode 2 is entered and
H1P lights.
During the setting mode 1 is displayed, “In low noise operation” and “In demand control” are
displayed.
2. Setting mode 2 (H1P on)
c
In setting 1, push and hold the BS1 (MODE button) for more than 5 seconds.
→
Setting
mode 2 is entered and H1P lights.
d
Push the BS2 (SET button) several times and match the LED display with the Setting No.
you want.
e
Push the BS3 (RETURN button) one time, and the present setting content is displayed.
→
Push the BS2 (SET button) several times and match the LED display with the setting
content (as shown below) you want.
f
Push the BS3 (RETURN button) two times.
→
Returns to
c
.
g
Push the BS1 (MODE button) one time.
→
Returns to the setting mode 1 and turns H1P off.
{
: ON
z
: OFF
9
: Blink
c
d
e
Setting
No.
Setting
contents
Setting No. indication
Setting No. indication
Setting
contents
Setting contents indication (Initial setting)
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
H1P H2P H3P H4P H5P H6P H7P
12
External
low noise /
Demand
setting
{
z
z
z
z
z
z
{
z
z
{
{
z
z
NO
(Factory
setting)
{
z
z
z
z
z
9
YES
{
z
z
z
z
9
z
22
Night-time
low noise
setting
{
z
{
z
{
{
z
OFF
(Factory
setting)
{
z
z
z
z
z
z
Mode 1
{
z
z
z
z
z
9
Mode 2
{
z
z
z
z
9
z
Mode 3
{
z
z
z
z
9
9
25
External
low noise
setting
{
z
{
{
z
z
{
Mode 1
{
z
z
z
z
z
9
Mode 2
(Factory
setting)
{
z
z
z
z
9
z
Mode 3
{
z
z
z
9
z
z
26
Night-time
low noise
start setting
{
z
{
{
z
{
z
PM 8:00
{
z
z
z
z
z
9
PM 10:00
(Factory
setting)
{
z
z
z
z
9
z
PM 0:00
{
z
z
z
9
z
z
27
Night-time
low noise
end setting
{
z
{
{
z
{
{
AM 6:00
{
z
z
z
z
z
9
AM 7:00
{
z
z
z
z
9
z
AM 8:00
(Factory
setting)
{
z
z
z
9
z
z
29
Capacity
precedence
setting
{
z
{
{
{
z
{
Low noise
precedence
(Factory
setting)
{
z
z
z
z
z
9
Capacity
precedence
{
z
z
z
z
9
z
30
Demand
setting 1
{
z
{
{
{
{
z
60 % of
rated power
consumption
{
z
z
z
z
z
9
70 % of
rated power
consumption
(Factory
setting)
{
z
z
z
z
9
z
80 % of
rated power
consumption
{
z
z
z
9
z
z
32
Normal
demand
setting
{
z
z
z
z
z
z
OFF
(Factory
setting)
{
z
z
z
z
z
9
ON
{
z
z
z
z
9
z
Setting mode indication section
Setting No. indication section
Set contents indication section
Summary of Contents for VRV III REYQ8PY1
Page 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701...
Page 59: ...Specifications Si37 701 48 Specifications...
Page 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit...
Page 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219...
Page 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH...
Page 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743...
Page 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742...
Page 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741...
Page 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A...
Page 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C...
Page 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E...
Page 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E...
Page 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E...
Page 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359...
Page 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1...
Page 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B...
Page 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C...
Page 423: ...Piping Installation Point Si37 701 412 Appendix...
Page 427: ...Example of Connection R 410A Type Si37 701 416 Appendix...
Page 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix...
Page 447: ...Si37 701 iv Index...
Page 451: ...Si37 701 viii Drawings Flow Charts...