Troubleshooting by Remote Controller
SiBE37-701
250
Troubleshooting
<Selection of setting item>
<Monitor mode>
<Confirmation of malfunction 1>
To enter the monitor mode, push the
MODE (BS1) button when in
“Setting mode 1”.
Push the SET (BS2) button and set
the LED display to a setting item.
Push the RETURN (BS3) button
once to display "First digit" of
malfunction code.
<Confirmation of malfunction 2>
Push the SET (BS2) button once to
display "Second digit" of malfunction
code.
Push the RETURN (BS3) button and
switches to the initial status of
“Monitor mode”.
∗
Push the MODE (BS1) button and
returns to “Setting mode 1”.
<Confirmation of malfunction 3>
Push the SET (BS2) button once to
display "malfunction location".
* Refer to Page 215 for Monitor mode.
* Refer to Page 215 for Monitor mode.
Detail
description
on next
page.
<Confirmation of malfunction 4>
Push the SET (BS2) button once to
display "master or slave 1 or slave 2"
and "malfunction location".
Malfunctions
Malfunction
code
Description of malfunction
Description of malfunction (PGF)
Remote
controller
Open phase and unbalanced power
supply
Unbalanced INV power supply voltage
P1
INV radiation fin temperature sensor
malfunction
INV fin thermistor malfunction
P4
Faulty combination of INV and fan
driver
Faulty combination of INV
PJ
Out of gas
Out-of-gas alarm
U0
Reversed phase
Reversed phase malfunction
U1
Reversed phase malfunction (ON)
Abnormal power supply voltage
Insufficient INV voltage
U2
INV open phase (single phase)
Abnormal charge of capacitor of INV
main circuit
Test run not carried out yet
Test run not carried out yet
U3
Faulty transmission between indoor
and outdoor units
IN-OUT transmission malfunction
U4
System malfunction
Faulty transmission between outdoor
units
Malfunction caused when mounting
the external control adapter
U7
Alarm given when mounting the
external control adapter
Malfunction caused between the
master and the slave 1
Malfunction caused between the
master and the slave 2
Multi REYQ models connected
Faulty address setting of slaves 1 and 2
4 or more outdoor units connected in
the same system
Erroneous address of slaves 1 and 2
Faulty transmission with other
systems
Other system or other unit in the same
system
U9
Faulty field setting
Excess indoor units connected
UA
Erroneous refrigerant used for indoor
unit
Faulty combination of outdoor units
Faulty independent installation
Faulty connection of former BS unit
Faulty connection between outdoor
and BS unit
Faulty connection between BS units
Wrong number of indoor units
connected to BS unit
Faulty system line
Wrong wiring (auto address error)
UH
Faulty transmission with accessory
equipment
Multi level converter malfunction
UJ
Multi level converter alarm
Multi level converter data malfunction
Multi level converter transmission
malfunction
Unmatched wiring/piping, no system
settings
Unmatched wiring/piping
UF
k
: ON
l
: Blink
h
: OFF
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...