Test Operation
SiBE37-701
178
Test Operation
[Remote controller malfunction code display]
Remote controller heating mode malfunction codes
Remote controller cooling mode malfunction codes
[Checks after adding refrigerant]
Are the stop valves for both liquid and gas open?
Is the amount of refrigerant, that has been added, recorded?
Error code
P8
recharge
operation
Close valve A immediately and press the TEST OPERATION button once.
The operation will restart from the charging mode judgement onwards.
P2
charge hold
Close valve A immediately. Check following items:
- Check if the gas side stop valve is opened correctly
- Check if the valve of the refrigerant cylinder is opened
- Check if the air inlet and outlet of the indoor unit are not
obstructed
After correcting the
abnormality, restart the
automatic charging procedure
again.
Error code
PA
,
PH
,
PC
replace
cylinder
Close valve A and replace the empty cylinder. When renewed, open valve A (the outdoor unit will
not stop operating).
The code on the display shows the unit where a cylinder is to be renewed:
PA
= master unit,
PH
= slave unit 1,
PC
= slave unit 2, flashing
PA
,
PH
and
PC
= all units
After recplacing the cylinder, open valve A again and continue the work.
In case of an outdoor multi system, replacing the refrigerant tank of the outdoor unit during
the refrigerant charging operation when the display on the remote controller is not
showing
PA
,
PH
or
PC
, may cause an abnormal stop of the refrigerant charging operation.
P8
recharge
operation
Close valve A immediately.
Restart the automatic charging procedure again.
P2
charge hold
Close valve A immediately. Check following items:
- Check if the high pressure/low pressure gas pipe, suction
gas pipe, liquid pipes and equalizer pipe stop valves are
opened correctly
- Check if the valve of the refrigerant cylinder is opened
- Check if the air inlet and outlet of the indoor unit are not
obstructed
- Check if the indoor temperature is not lower than 10°C DB
After correcting the abnormality,
restart the automatic charging
procedure again.
*
abnormal
stop
Close valve A immediately. Confirm the malfunction code by
the remote controller and correct the abnormality by following
the "Correcting after abnormal completion of the test operation"
on page 25.
Make sure to open the stop valves after charging the refrigerant.
Operating with the stop valves closed will damage the compressor.
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...