Selection of Pipe Size, Joints and Header
Si39-502A
276
Appendix
∗
Note 1
When overall equivalent pipe length is 90 m or more, the size of the main gas and liquid pipes (Outdoor unit-first branch kit) must be increased.
∗
Note 2
Allowable length after the first refrigerant branch kit to indoor units is 40 m or less, however it can be extended up to
90
m
if all the following conditions are satisfied. (In case of
" Branch with refnet joint "
)
n
Diameter of above case
Model
RXYQ8MY1K(E), YLK(E)
RXYQ10MY1K(E), YLK(E)
RXYQ16MY1K(E), YLK (E)
Gas
φ
22.2
φ
25.4
φ
31.8
Liquid
φ
12.7
φ
12.7
φ
15.9
Model
RXYQ18MY1K(E), YLK(E)
RXYQ20MY1K(E), YLK(E)
RXYQ24MY1K(E), YLK(E)
Gas
φ
31.8
φ
31.8
Not
Increased
Liquid
φ
19.1
φ
19.1
φ
19.1
Model
RXYQ26MY1K(E), YLK(E)
RXYQ28MY1K(E), YLK(E)
RXYQ30MY1K(E), YLK(E)
Gas
φ
38.1*
φ
38.1*
φ
38.1*
Liquid
φ
22.2
φ
22.2
φ
22.2
a
A
B
C
D
E
F
G
b
c
d
e
f
g
h
i
j
k
l
m
n
1
2
3
4
5
6
7
8
H1
P
Outdoor unit
REFNET joint (A-G)
Indoor units (1-8)
Required Conditions
1. It is necessary to increase the pipe size between
the first branch kit and the final branch kit.
(Reducers must be procured on site)
2. For calculation of Total extension length,
the actual length of above pipes must be doubled.
(except main pipe)
3. Indoor unit to the nearest branch kit
≤
40 m
4. The difference between
[Outdoor unit to the farthest indoor unit] and
[Outdoor unit to the nearest indoor unit]
≤
40 m
Example Drawings
8 b + c + d + e + f + g + p
≤
90 m
increase the pipe size of b, c, d, e, f, g
a + b
×
2 + c
×
2 + d
×
2 + e
×
2 + f
×
2 + g
×
2
+ h + i + j + k + l + m + n + p
≤
510 m
h, i, j ....... p
≤
40 m
The farthest indoor unit 8
The nearest indoor unit 1
(a + b + c + d + e + f + g + p) - (a + h)
≤
40 m
Increase the pipe size as follows
φ
6.4
→
φ
9.5
φ
12.7
→
φ
15.9
φ
19.1
→
φ
22.2
φ
34.9
→
φ
38.1
φ
9.5
→
φ
12.7
φ
15.9
→
φ
19.1
φ
28.6
→
φ
31.8
*
If available on the site, use this size.
Otherwise it can not be increased.
Summary of Contents for VRV II RXYQ8MY1K
Page 53: ...Specifications Si39 502A 42 Specifications...
Page 143: ...Field Setting Si39 502A 132 Test Operation...
Page 258: ...Si39 502A Wiring Diagrams for Reference Appendix 247 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 260: ...Si39 502A Wiring Diagrams for Reference Appendix 249 FXKQ25M 32M 40M 63MVE 3D039564A...
Page 264: ...Si39 502A Wiring Diagrams for Reference Appendix 253 FXMQ40M 50M 63M 80M 100M 125MVE 3D039620A...
Page 265: ...Wiring Diagrams for Reference Si39 502A 254 Appendix FXMQ200M 250MVE 3D039621A...
Page 266: ...Si39 502A Wiring Diagrams for Reference Appendix 255 FXHQ32M 63M 100MVE 3D039801C...
Page 267: ...Wiring Diagrams for Reference Si39 502A 256 Appendix FXAQ20M 25M 32M 40M 50M 63MVE 3D034206A...
Page 269: ...Wiring Diagrams for Reference Si39 502A 258 Appendix FXUQ71M 100M 125MV1 3D044973...
Page 270: ...Si39 502A Wiring Diagrams for Reference Appendix 259 FXAQ20MH 25MH 32MH 40MH 50MHV1 3D046348A...
Page 271: ...Wiring Diagrams for Reference Si39 502A 260 Appendix FXLQ20MH 25MH 32MH 40MH 50MHV1 3D046787A...
Page 272: ...Si39 502A Wiring Diagrams for Reference Appendix 261 BEVQ50MVE 3D046579A Notes...
Page 273: ...Wiring Diagrams for Reference Si39 502A 262 Appendix BEVQ71M 100M 125MVE 3D044901A Notes...
Page 285: ...Piping Installation Point Si39 502A 274 Appendix...
Page 293: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 502A 282 Appendix...
Page 307: ...Si39 502A iv Index...